The SR-76 Relay test set



INSULATION RESISTANCE TEST

 A test that may be run on all types of relays to determine the  conditions of the insulation.  In this test                   
1,000VDC is applied between relay connections that are brought to the outside of the relay and the frame of the        
relay.  It is of an infinite quality as read in the megohmeter, the cause is found and remedied.

ZERO CHECK

 A test that is conducted on any relay that has a time dial.  The purpose is to determine the time dial reading        
when the relay is fixed and moving contacts are closed by the manual rotation of the time dial toward zero.  (Primary  
ran or acceptance test or new test).

PICK UP TEST

 A test conducted on relays to determine the minimum or maximum current, voltage, power or frequency that will   
allow the relay operation and closure of the relay.  In case of a time Overcurrent relay, its contacts should                  
eventually creep to a closed position with a magnitude of current introduced in its induction coil equal to the top         
setting.  The pick up test on a voltage relay is made in much the same manner.

TIME CHARACTERISTICS OR TIMING TEST

 A test run to determine the elapsed time for relay operations  with a specific abnormal quantity of current,            
voltage, power or frequency.  In the case of a time Overcurrent relay, one or more timing test are made at anywhere  
from two to ten times the top setting to verify the time Overcurrent characteristics of the relay.  One timing point         
should be specified in the prescribed settings.  Tests should be made with the relay in its panel and case and the      
time test run at the calibration settings.  A timing test should be made on most types of relays.

INSTANTANEOUS TEST

 Some protective relays are instantaneous in operation or may have a separate instantaneous element.  In this    
context, the term instantaneous means having no intentional delay.  If used, this specific pick up on the                      
instantaneous element should be set by test.  An instantaneous element at two times pick up should operate              
between 0.016 and 0.030 seconds.

TEST OF TARGET AND SEAL IN CIRCUIT

Most types of protective relays have a combination target and seal in unit.  The target indicates that the relay      
has operated.  The seal in unit is adjustable to pick up at either 0.2 or 2.0 amperes.  The setting for the seal in unit   
must be specified with the relay settings.

*It should be verified by test that the contacts will seal in (hold in close position) with the minimum specified DC          
  current applied to the seal in unit.

TEST OF TRIPPING CIRCUIT

 A test should be made, preferably at the time of the testing of the relays, to verify that operation of the relay        
contacts will cause the breaker to trip.

 
The protective relays are one of the most important pieces of equipment in          
your plants.  The failure of the units to operate properly usually results in the loss     
of major equipment and a larger period of down time.
Relay being tested

A General Electric Over Current Relay being Tested and Calibrated in our repair shop, Southern
Substation can test and calibrate all of your relays we also can rebuild or supply you with replacement
relay's to fill all of your needs Please contact us for more information.
Return to the Previous Page on Relay Testing
Protective Relay
G.E. Overcurrent Relay
Relay testing Page two.